9.2   Whole-Building Ventilation

SWS Details: 6.6201.1 Installed System Air Flow

Most homes in North America currently rely on air leakage for ventilation. The American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) publishes ventila­tion standards. Their current standard, ASHRAE 62.2-2013, requires fan-powered ventilation in all homes, as well as local exhaust ventilation in kitchens and bathrooms. The standard allows for natural infiltration (air leakage) to contribute toward the required whole-building ventilation rate. The standard also allows for whole-building fan-powered ventilation to make up for insufficient local ventilation.

Refer to the standard for more details, guidance, and exceptions that are beyond the scope of this field guide. http://www.tech­street.com/ashrae/products/1855284. Residential Energy Dynamics provides a free online tool to help calculate ASHRAE 62.2-2013 ventilation rates. http://residentialenergydynam­ics.com

If you air-seal homes during weatherization, you may need to install whole-building mechanical ventilation systems under ASHRAE 62.2–2013, which has 3 components.

       Whole-building ventilation requirement.

       Local ventilation requirement.

       Natural infiltration credit.

9.2.1   Whole-Building Ventilation Requirement

SWS Details: 6.6201.1 Installed System Air Flow, 6.9901.1 Supplemental Ventilation Information—ASHRAE 62.2, 6.6204.1 Commissioning Existing Exhaust or Supply Ventilation Systems, 6.6201.2 Primary Ventilation Air Flow between Rooms

To comply with ASHRAE 62.2–2013, you can use either the for­mula or the table shown here to determine the whole-building ventilation airflow requirement. You can provide this fan-pow­ered airflow in a number of ways.

       A dedicated exhaust or supply fan running continuously or cycling by automatic control.

       A bathroom or kitchen exhaust fan running continuously or cycling by automatic control.

       A central air handler drawing filtered outdoor air into its return.

       A balanced ventilation system such as a heat-recovery ven­tilator (HRV) or energy-recovery-ventilator (ERV).

If any room in the house exceeds ±3 pa pressure with reference to the outdoors when all interior doors are closed and while the ventilation system is operating, then install transfer grilles or jumper ducts as needed to reduce the room to outdoors pressure difference to less than ±3 pa. SWS Detail: 6.6201.2 Primary Ven­tilation Air Flow between Rooms

Option 1: The Formula

If you want to install the minimum ventilation capacity, use these steps to follow the formula option.

1.      Determine the floor area of the conditioned space of the home in square feet (Afloor).

2.      Determine the number of bedrooms (Nbr).

3.      Insert these numbers in the formula below.

Ventilation00001.jpg

 

Option 2: The Table

You can also determine the fan airflow under ASHRAE 62.2–2013 using the table shown here. This option will always provide a higher ventilation rate than the formula.

Table 9-1:         CFM Requirements for Whole-Building Ventilation

Floor Area (ft2)

Number of Bedrooms

1

2

3

4

5

<500

30

38

45

53

60

5011000

45

53

60

68

75

10011500

60

68

75

83

90

1501–2000

75

83

90

98

105

2001–2500

90

98

105

113

120

2501–3000

105

113

120

128

135

3001–3500

120

128

135

143

150

3501–4000

135

143

150

158

165

4001–4500

150

158

165

173

180

4501–5000

165

173

180

188

195

Fan flow in CFM. From ASHRAE Standard 62.2-2013, Table 4.1a

9.2.2   Local Exhaust Ventilation Requirement

SWS Detail: 6.6201.1 Installed System Air Flow, 6.6005.2 Kitchen Range

There are two options for complying with the ventilation requirements for kitchens and bathroom. Demand controlled exhaust, or continuous exhaust.

       For demand controlled exhaust specify a minimum of 100 CFM for the kitchen, and 50 CFM for each bathroom.

       For continuous exhaust specify a minimum of 20 CFM for each bathroom, and 5 ACH for the kitchen (based on vol­ume).

Local Exhaust Deficit

If the existing kitchen or bathroom ventilation doesn’t meet the requirements in “Local Exhaust Ventilation Requirement” on page 361, you may adjust the whole-building ventilation rate to compensate for the local airflow deficits. Follow these steps to calculate the local-ventilation deficit in CFM that must be added to the whole-building ventilation rate.

1.      Determine the total local exhaust ventilation require­ment for all kitchens and bathrooms.

2.      Measure the delivered airflow of existing kitchen or bathroom exhaust fans using flow hood, flow grid, or other airflow measuring device. Subtract this amount from the total local exhaust ventilation requirement.

3.      If the local jurisdiction allows for operable windows to provide for local ventilation, subtract 20 CFM for each kitchen or bathroom that has an operable window.

The result of these steps is the local exhaust ventilation deficit in CFM. Add 1/4 of this deficit to the required whole-building ven­tilation rate.

TECfanBoxSm.jpg

 

9.2.3   Infiltration Credit

ASHRAE 62.2-2013 allows for infiltration to contribute to the building’s ventilation. It is possible that infiltration will meet the entire whole-building ventilation requirement for very leaky buildings. For moderately leaky buildings, infiltration may con­tribute a portion of the building’s ventilation. The amount of the infiltration credit is determined with a blower door test and weather data based on the building’s location. Calculating the infiltration credit is complicated. To simplify the calculations, use the RED Calc Free online tool at http://www.residentialener­gydynamics.com/and select the “Use Local Ventilation Alterna­tive Compliance” option.