Chapter 6:                      Floors and Foundations

The importance of defining the thermal boundary at the build­ing’s lower reaches depends on how much of the building’s heat loss is moving through the foundation or floor. The building’s thermal boundary may not be obvious because of the lack of insulation at both the floor and the foundation. The building owner and energy auditor must choose where to insulate and air seal if these ECMs are cost-effective.

Either the first floor or the foundation wall is the thermal boundary. After choosing, cost effectively air seal and insulate the chosen thermal boundary.

6.1   Thermal-Boundary Decisions: Floor or Foundation

SWS Detail: 3.1401.1 Basements Connected to Crawl Spaces—Sealing and Insulating

The results of air-barrier tests can help in selecting the thermal boundary’s location. See Air Leakage Diagnostics

Moisture problems, the location of heating and cooling equip­ment, and the necessity of crawl-space venting are other import­ant considerations.

HwrtCS-25.jpg

 

The tables presented next summarize the decision factors for choosing between the floor and the foundation wall as the air barrier. You may also encounter situations that aren’t addressed here.

When a home has a basement and crawl space connected, both Table Table 6-1:   .  and Table Table 6-2:   .  are relevant to the decision-making process of selecting the air barrier and thermal boundary, if insulation is cost-effective. A basement may even be divided from its adjoining crawl space to enclose the basement within the thermal boundary and to place the crawl space outside the thermal boundary. In New Hampshire the basement wall is almost always the appropriate thermal boundary.

Table 6-1:         Crawl Space: Where Is the thermal boundary?

Factors favoring foundation wall

Factors favoring floor

Ground moisture barrier and good perimeter drainage pres­ent or planned

Dry crawl space with ground moisture barrier installed during weatherization

Foundation walls test tighter than floor

Floor air-sealing and insulation are reasonable options, consider­ing access and obstacles

Vents can be closed off

Floor tests tighter than founda­tion walls

Furnace, ducts, and water pipes located in crawl space

No furnace or ducts present

Concrete or concrete block walls are easily insulated

Building code or code official for­bids closing vents

Floor air-sealing and insulation would be more difficult than sealing and insulating the foun­dation

Rubble masonry foundation wall

Foundation wall is insulated

Floor is already insulated

Warm, damp homesite + climate

Cooler, drier homesite + climate

Table 6-2:         Unoccupied Basement: Where Is the thermal boundary?

Favors foundation wall

Favors floor

Ground drainage and no existing moisture problems

Damp basement with no solu­tion during weatherization

Interior stairway between house and basement

Floor air-sealing and insulation is a reasonable option, consider­ing access and obstacles

Ducts and furnace in basement

No furnace or ducts present

Foundation walls test tighter than the floor

Floor tests tighter than founda­tion walls

Basement may be occupied some day

Exterior entrance and stairway only

Laundry in basement

Rubble masonry foundation walls

Floor air-sealing and insulation would be very difficult

Dirt floor or deteriorating con­crete floor

Concrete floor

Cracked foundation walls

6.2   Air Sealing Foundations and Floors

The floor and foundation are complex structures that can be dif­ficult to air seal. This section describes the most problematic air leakage location in the floor and foundation, and how to seal them.

6.2.1   Garages Underneath Living Areas

SWS Detail: 3.1501.1 Penetrations, Cracks, and Doors Between Garage and House

Whenever a garage is in a subspace below living areas, the effec­tiveness of air sealing is essential for three objectives.

1.      Block air pollutants,

2.      Create a fire barrier,

3.      Save energy by separating the unconditioned garage from the building’s conditioned zones.

Air-sealing a garage area is straightforward although this task can consume a lot of materials.

       For wood-frame structures, use fire-taped drywall throughout the surface area of the garage after sealing leaks in the floor above and the in the top plate of the walls.

       For concrete and masonry structures, carefully seal cracks and penetrations with compatible materials such as mortar and caulk designed for masonry joints.

6.2.2   Plumbing Penetrations

SWS Detail: 3.1001.1 Penetrations and Chases, 3.1001.2 Chase Capping

Seal gaps with expanding foam or caulk. If the gap is too large, stuff it with fiberglass insulation, and spray foam over the top to seal the surface of the plug.

     Fit large openings with a rigid patch bedded in a sealant like latex caulk or foam tape, which isn’t an adhesive.

     Screw the patch in place, so that a plumber can remove the screws if necessary for access.

     Seal holes and gaps around pipes with expanding foam or caulk.

FloorsFoundations00003.jpg

 

6.2.3   Stairways to Unconditioned Areas

SWS Detail: 3.1002.1 Interior with Sloped Ceiling, 3.1002.2 Stairwell to Attic—Door at Bottom with No Ceiling Above, 3.1002.3 Stairwell to Attic—Door at Top with Finished Ceiling Above

A variety of stairways and hatchways provide access from the building to an unconditioned basement.

The following components of these stairways may need air seal­ing and insulation depending on whether they are at the thermal boundary.

       The risers and treads of the stairways

       The surrounding triangular walls

       Vertical or horizontal doors or hatches

       The framing and sheeting surrounding the doors or hatches

       Sloping ceilings above the stairways

Consider the following air-sealing measures.

     Study the geometry of the stairway and decide where to establish the air barrier and install the insulation.

     Weatherstrip around doors and hatches if the door or hatch is at the air or pressure boundary.

     Seal the walls, stair-stringer space, and ceiling if they are at the thermal boundary.

     Seal gaps around door frame or hatch frame perimeters with one-part foam, two-part foam, or caulking.

FloorsFoundations00006.jpg

 

6.2.4   Incomplete Finished Basements

Discontinuous wall segments can allow heated basement air to circumvent the finished and insulated wall, carrying heat with it. Complete the finished walls or at least install air barriers between finished living area and unconditioned area between the insulated wall and the foundation wall. Here are two sugges­tions.

     Bridge the gap with wood sheeting, bedded in sealant, and caulk the crack around four sides of this long narrow patch.

     Stuff the gap with pieces of fiberglass batt and spray two-part foam over the gap, at least an inch thick.

See also Basement Insulation

BsmtWallFlaw.jpg

 

6.2.5   Cantilevered Floors

SWS Detail: 3.1802.2 Exterior Overhangs Communicating to or Through Pressure Boundary, 4.1301.5 Cantilevered Floor—Batt Installation

Floors that hang over their lower story are called cantilevered floors. The underside of the overhanging floor can leak consid­erably. Many balconies and bay windows have cantilevered floors that leak air into a building’s floor cavity.

CantileversConst.jpg

 

     Remove a piece of soffit under the overhanging floor to determine the condition of insulation and air barrier.

     Stuff the overhanging floor with fiberglass batts or blown fibrous insulation.

     Bed the sheeting underneath the overhanging floor in sealant where possible. Caulk joints and seams where the sheeting isn’t bedded in sealant.

     Seal any ducts you find in the cantilevered floor sections.

See also Installing Floor Insulation

6.3   Preparing for Foundation or Floor Insulation

SWS Detail: 4.1402.2 Basement Wall Insulation—No Groundwater Leakage, 4.1402.3 Basement Wall Insulation—Groundwater Leakage, 2.0404.4 Basements—Dehumidification

Floor and foundation insulation can increase the likelihood of moisture problems. Installers should take all necessary steps to prevent moisture problems from ground moisture before install­ing insulation.

6.3.1   Rim-Joist Insulation and Air-Sealing

SWS Detal: 4.1401.1 Band/Rim Joists—Spray Polyurethane Foam (SPF) Installation, 4.1401.2 Band/Rim Joists – Insulation other than Spray Polyurethane Foam

The rim-joist spaces at the perimeter of the floor are a major weak point in the air barrier and insulation. Insulating and air sealing both the rim joist and longitudinal box joist are appro­priate either as individual procedures or as part of floor or foun­dation insulation.

Air seal stud cavities in balloon-framed homes as a part of insu­lating the rim joist. Air seal other penetrations through the rim before insulating. Two-part spray foam is the most versatile air sealing and insulation system for the rim joist because spray foam air seals and insulates in one step.

Polystyrene or polyurethane rigid board insulation are also good for insulating and air sealing the rim joist area. When the rim joist runs parallel to the foundation wall, the cavity may be air sealed and insulated with methods similar to those as shown here.

If you leave the spray foam exposed, it should have a flame spread of 25 or less and be no more than 3.25 inches thick according to the IRC. In habitable spaces, cover all foam with a thermal barrier such as drywall or use an insulation product that doesn’t require a thermal barrier like mineral wool boards and foil-faced PIC.

FloorsFoundations00013.jpg

 

Don’t use fiberglass batts to insulate between rim joists because air can move around the fiberglass, causing condensation and encouraging mold on the cold rim joist. If you use foam to insu­late between the rim joists, use liquid foam sealant to seal around the edges of the rigid foam.

6.3.2   Installing Floor Insulation

SWS Details: 4.1301.1 Standard Floor System—Batt Installation, 4.1301.2 Standard Floor System—Loose Fill with Netting, 4.1301.3 Standard Floor System—Loose Fill with Rigid Barrier, 4.1301.4 Dense Pack Floor System with Rigid Barrier, 4.1301.7 Pier Construction Subfloor Insulation—Loose Fill with Rigid Barrier, 4.1301.8 Pier Construction Subfloor Installation—Dense Pack with Rigid Barrier, 4.1301.9 Open Floors Over Unconditioned Space and Cantilevered Floors, Floors Over Garages, Floors Over Unconditioned Crawl Spaces—Spray Polyurethane

Before installing floor insulation, make the following prepara­tions.

     Seal air leaks in the floor from the living space or the crawl space or basement, as opportunity allows.

     Seal and insulate ducts remaining in the crawl space or unconditioned basement.

     Identify electrical junction boxes, plumbing valves and drains before insulating and provide access to them.

     Insulate water lines in cold climates if they protrude below the insulation.

Blowing Floor Insulation

The best way to insulate a floor cavity is to completely fill each joist cavity with fiberglass insulation. Blowing fiberglass insula­tion is the easiest way to achieve complete coverage because the blown fiberglass is able to surround obstructions and penetra­tions better than fiberglass batts. Avoid blown cellulose because of its weight, moisture absorption, and tendency to settle.

     Cover the entire under-floor surface with a vapor perme­able supporting material such as: dust-free fabric insula­tion restraint or equivalent vapor-permeable and drain-able material. Do not use house wrap sheeting materials to hold up floor insulation.

     Use wood strips to support the flexible or semi-flexible support material unless that material with its fasteners can support the floor insulation without sagging.

Blwn_Flr_Insulation.jpg

 

     Install rock wool or fiberglass blowing wool through V-shaped holes in the air barrier.

     Use a fill tube for installing the blown insulation. Insula­tion must travel no more than 12 inches from the end of the fill tube.

     Seal all penetrations in the air barrier with a tape, approved for sealing seams in the air-barrier material.

InsulFlrCavity.jpg

 

6.3.3   Installing Fiberglass Batt Floor Insulation

SWS Detail: 4.1301.1 Standard Floor System—Batt Installation, 4.1301.5 Cantilevered Floor—Batt Installation, 4.1301.6 Pier Construction Subfloor Insulation—Batt Installation with Rigid Barrier

Observe these material and preparation specifications for insu­lating under floors.

     Choose unfaced batts for insulating floors.

     Seal all significant air leaks through the floor before insu­lating the floor, using strong airtight materials.

     Batt thickness must fill the complete depth of each cavity.

     Batts must be neatly installed, fitting tightly together at joints, fitting closely around obstructions, and filling all the space within the floor cavity.

     Crawl-space access doors, adjacent to a conditioned space, must be insulated to at least R-21 for horizontal openings and to at least R-15 for vertical openings.

     Crawl-space access doors, adjacent to a conditioned space, must be effectively weatherstripped.

Installation Specifications for Batts in Floor Cavities

Batt insulation, installed in floors, must be supported by twine, wire, wood lath or other suitable material that keeps the insula­tion touching the floor. Friction-fit fiberglass batts supported by self-supporting wire insulation supports aren’t good practice. Fasteners for floor insulation must resist gravity, the weight of insulation, and moisture condensation.

     Install batts in continuous contact with the subfloor.

     Cut the batts accurately and squarely. An electric carving knife is an excellent tool for this purpose.

Use one of the following 4 restrainer materials to keep the fiber­glass batts in the floor cavity.

1.      Install standard wood lath (1/4 inch by 1 inch) or nomi­nal one-inch lumber. Install the lath or lumber perpen­dicular to joists 12 inches apart for joists on 24-inch centers and 18 inches apart for joists on 16-inch cen­ters.

2.      Install non-stretching polypropylene or polyester twine.

3.      Install copper or stainless steel wire with a minimum diameter of 0.04 inches or size 18 AWG.

Observe these requirements about installation and fasteners for the restrainers.

       Fasten lath or a rigid barrier with screws, nails, or power-driven staples. The fastener should penetrate the joist 3/4 inch or more.

       Install twine or wire in a zig-zag pattern.

       Install power-driven staples over the twine or wire 12 inches apart for joists on 24-inch centers and 18 inches apart for joists on 16-inch centers. The staples must pene­trate the wood joists by at least 5/8 inch. Don’t hand staple the restrainer.

.

FloorInsulatioMounting.jpg

6.3.4   Crawl-Space Wall Insulation

SWS Detail: 2.0107.2 Basements and Crawl Spaces—Pre-Work Qualifications, 4.1402.2 Basement Wall Insulation—No Groundwater Leakage, 4.1402.3 Basement Wall Insulation—Groundwater Leakage, 4.1402.1 Closed Crawl Spaces —Wall Insulation, 3.1402.2 Closed Crawl Spaces —Air Sealing Foundation Vents

Crawl-space foundation insulation is only worthwhile if you can seal the existing foundation vents.

Materials for Crawl-Space Insulation

Retrofit foundation insulation is usually installed on the inside of the foundation walls. Contractors undertake this retrofit for both energy savings and moisture control. Observe these insula­tion specifications for insulating foundation walls.

       Any foam foundation-wall insulation should be labeled ASTM E84 or UL 723 with a flame spread of less than 25 and smoke developed value of less than 450.

       Foam insulation must be protected by intumescent paint or another ignition barrier if not labeled ASTM E84 or UL 723.

       Local building officials may approve other foam materials based on product labels such as NFPA 286, FM 4880, UL 1040, or UL 1715.

       Unfaced mineral fiber insulation, greater than 5 pounds per cubic foot in density. Although expensive, mineral wool board is probably the best choice because it is vapor perme­able and non combustible.

       Metal fasteners should carry a label of ASTM B 695 Class 55.

These insulation products might meet some of the above speci­fications.

       Foil-faced polyisocyanurate

       Expanded polystyrene foam board.

       Two-part high-density spray polyurethane foam with fire-retardant specifications as listed above. See Fire Protection for Foam Insulation

       Unfaced rock wool board or fiberglass board.

.

Rim2partCS.jpg

Consider these issues with the use of fibrous insulation in crawl spaces.

       Fiberglass batts or blankets are poor choices for foundation insulation because their facing is a vapor retarder. The fac­ing can trap moisture in the fiberglass between the founda­tion wall and the facing.

       Sprayed fiberglass and cellulose are easily damaged by moisture, mechanical abrasion, and adhesive failure.

Safety and Durability

Consider the following issues when insulating foundation walls.

     Secure outdoor access hatches to foundation walls. If the foundation walls are insulated, also insulate any crawl-space access hatch with foam to the same R-value of the foundation wall.

     Remove obstacles and debris from crawl space before ret­rofit.

     If an open-combustion appliance is located in a crawl space, verify that outdoor combustion air is available to the appliance.

     When insulating crawl-space walls, consult the local build­ing inspector about acceptable ventilation options if in doubt. See Crawl Space Ventilation

In regions affected by termites, carpenter ants, and similar insects consider these suggestions.

     Leave a termite-inspection zone between the foundation and the rim-joist insulation.

     Apply insulation with moisture control measures, pesti­cide, or baiting.

     Consult with experts to ensure that the insulation, air seal­ing materials, and moisture barrier don’t provide a conduit for insects to infest the wood floor.

SPFcrlSpce.jpg

 

6.3.5   Basement Insulation

SWS Detail: 4.1402.2 Basement Wall Insulation—No Groundwater Leakage, 4.1402.3 Basement Wall Insulation—Groundwater Leakage

Before installing basement wall insulation, inspect for moisture problems and take appropriate action to solve moisture prob­lems.

     Check for bulk-water problems like puddling around the foundation or malfunctioning gutters and downspouts.

     Remove obstacles and debris from the basement.

     Repair structural cracks in foundation walls.

     Install a drainage system with a sump and outdoor drain­age as appropriate to solve major moisture problems.

     Do not insulate more than two feet below the outdoor grade unless you are certain the backfill on the outside of the foundation wall drains well and that exterior drains at the foundation footings are properly installed and work­ing.

Basement wall is often installed ineffectively because of the installers’ incomplete understanding about moisture problems.

 

Stripped Foam Basement Insulation

Polystyrene foam is an excellent choice for insulating smooth basement walls. Do not insulate more than two feet below the outdoor grade unless you are certain the backfill on the outside of the foundation wall drains well and that exterior foundation drains at the foundation footings are properly installed and working.

You can order either expanded polystyrene or extruded polysty­rene equipped with grooves for fastening strips, spaced apart on 16-inch or 24-inch centers. Stripped foam sheets may be the eas­iest and most satisfactory way to insulate below-grade basement walls. Do these procedures to install 2-inch stripped foam on a foundation wall.

     Apply walnut-sized globs of adhesive to the back of the sheet on one-foot centers. Use a foam-compatible adhesive and follow the instructions on the container.

     Install at least two concrete screws or two powder-driven nails in each strip, 24 inches from the bottom and top.

FloorsFoundations00026.jpg

 

     Wherever an electrical box is needed, install it between two sheets if possible because it’s easier to run the wire between sheets than toward the center of a sheet. Install an electrical box backed by a piece of wood that sets the box out from the foam a half inch. Use construction adhesive and a concrete screw to fasten the box in place.

     Leave a half-inch gap at the bottom of the polystyrene sheets to run wire. Run the wire along the floor and up into the boxes. If flooding is a possibility, run the wire at the ceiling and down into boxes on the wall.

     Seal the bottom gap and other gaps in the foam sheeting with one-part foam.

     Glue the drywall using the same adhesive and pattern. Screw the drywall to each wooden strip with one-inch drywall screws.

Exterior Foam Foundation Insulation

If installed at the exterior, as during new construction, use dura­ble water-resistant insulation such as blue or pink extruded polystyrene or high-density (2 pcf) expanded polystyrene. For portions that are exposed above ground level and six inches below ground, you’ll need to provide mechanical and moisture protection such as sheet metal or fiberglass panels. For areas more than 6 inches below grade, there are asphalt-based sealants for the foam that are applied with a paint roller.

 

6.4   SWS Alignment

Field Guide Topic

SWS Detail

6.1: Thermal-Boundary Deci­sions: Floor or Foundation - Pg. 189

3.1401.1 Basements Connected to Crawl Spaces—Sealing and Insulating

6.2: Air Sealing Foundations and Floors - Pg. 191

N/A

6.2.1: Garages Underneath Liv­ing Areas - Pg. 191

3.1501.1 Penetrations, Cracks, and Doors Between Garage and House

6.2.2: Plumbing Penetrations - Pg. 192

3.1001.1 Penetrations and Chases,
3.1001.2 Chase Capping

6.2.3: Stairways to Uncondi­tioned Areas - Pg. 193

3.1002.1 Interior with Sloped Ceiling,
3.1002.2 Stairwell to Attic—Door at Bottom with No Ceiling Above,
3.1002.3 Stairwell to Attic—Door at Top with Finished Ceiling Above

6.2.4: Incomplete Finished Basements - Pg. 196

N/A

6.2.5: Cantilevered Floors - Pg. 197

3.1802.2 Exterior Overhangs Communicating to or Through Pressure Boundary,

4.1301.5 Cantilevered Floor—Batt Installation

6.3: Preparing for Foundation or Floor Insulation - Pg. 198

4.1402.2 Basement Wall Insulation—No Groundwater Leakage,
4.1402.3 Basement Wall Insulation—Groundwater Leakage,
2.0404.4 Basements—Dehumid­ification

6.3.1: Rim-Joist Insulation and Air-Sealing - Pg. 198

4.1401.1 Band/Rim Joists—Spray Polyurethane Foam (SPF) Installation,
4.1401.2 Band/Rim Joists – Insulation other than Spray Polyurethane Foam

6.3.2: Installing Floor Insulation - Pg. 200

4.1301.1 Standard Floor System—Batt Installation,
4.1301.2 Standard Floor System—Loose Fill with Netting,
4.1301.3 Standard Floor System—Loose Fill with Rigid Barrier,
4.1301.4 Dense Pack Floor System with Rigid Barrier,
4.1301.7 Pier Construction Subfloor Insulation—Loose Fill with Rigid Barrier,
4.1301.8 Pier Construction Subfloor Installation—Dense Pack with Rigid Barrier,
4.1301.9 Open Floors Over Unconditioned Space and Cantilevered Floors, Floors Over Garages, Floors Over Unconditioned Crawl Spaces—Spray Polyurethane

6.3.3: Installing Fiberglass Batt Floor Insulation - Pg. 202

4.1301.1 Standard Floor System—Batt Installation, 4.1301.5 Cantilevered Floor—Batt Installation,
4.1301.6 Pier Construction Subfloor Insulation—Batt Installation with Rigid Barrier

6.3.4: Crawl-Space Wall Insulation - Pg. 204

 2.0107.2 Basements and Crawl Spaces—Pre-Work Qualifica­tions,
4.1402.2 Basement Wall Insula­tion—No Groundwater Leakage,
4.1402.3 Basement Wall Insula­tion—Groundwater Leakage,
4.1402.1 Closed Crawl Spaces —Wall Insulation
3.1402.2 Closed Crawl Spaces —Air Sealing Foundation Vents

6.3.5: Basement Insulation - Pg. 207

4.1402.2 Basement Wall Insulation—No Groundwater Leakage,
4.1402.3 Basement Wall Insulation—Groundwater Leakage