Chapter 7: Floors and Foundations
The importance of defining the thermal boundary at the building’s lower reaches depends on how much of the building’s heat loss is moving through the foundation or floor. The building’s thermal boundary may not be obvious because of the lack of insulation at both the floor and the foundation. The building owner and energy auditor must choose where to insulate and air seal if these ECMs are cost-effective.
Either the first floor or the foundation wall is the thermal boundary. After choosing, air seal and insulate the chosen thermal boundary.
See “Material and Sealant Specs” on page 112.
7.1 Thermal-Boundary Decisions: Floor or Foundation
SWS Detail: 4.03 Floors; 3 Air Sealing; 3.0101 General Air Sealing; 3.0102 Specific Air Sealing; 3.0104 Foundation Spaces |
The results of air-barrier tests can help in selecting the thermal boundary’s location. See “Air Leakage Diagnostics” on page 547.
Before you can confidently air seal a building assembly, you must often decide which of two assemblies — the foundation walls or the floor for example — to air seal and insulate.
Moisture problems, the location of heating and cooling equipment, and the necessity of crawl-space venting are other important considerations.
The tables presented next summarize the decision factors for choosing between the floor and the foundation wall as the air barrier. You may also encounter situations that aren’t addressed here.
When a home has a basement and crawl space connected, both Table 6-1 below and Table 7-2 on page 220 are relevant to the decision-making process of selecting the air barrier and site for insulation, if insulation is cost-effective. A basement may even be divided from its adjoining crawl space to enclose the basement within the thermal boundary and to place the crawl space outside the thermal boundary.
7.2 Air Sealing Foundations and Floors
SWS Detail: 3 Air Sealing; 3.0101 General Air Sealing; 3.0102 Specific Air Sealing; 3.0104 Foundation Spaces |
The floor and foundation are complex structures that can be difficult to air seal. This section describes the most problematic air leakage locations in the floor and foundation, and how to seal them.
See “Material and Sealant Specs” on page 112.
7.2.1 Garages Underneath Living Areas
Whenever a garage is in a subspace below living areas, the effectiveness of air sealing is essential for three objectives.
1. Block air pollutants,
2. Create a fire barrier,
3. Save energy by separating the unconditioned garage from the building’s conditioned zones.
Air-sealing a garage area is straightforward although this task can consume a lot of materials.
• For wood-frame structures, use fire-taped drywall throughout the surface area of the garage after sealing leaks in the floor above and the in the top plate of the walls.
• For concrete and masonry structures, carefully seal cracks and penetrations with compatible materials such as mortar and caulk designed for masonry joints.
SWS Detail: 3.0101.1 Air Sealing Holes; 3.0104.1 Closed Crawlspace Air Sealing; 3.0104.3 Slab Foundation Sealing; 3.0104.4 Covers for Intentional Slab Penetrations |
Seal gaps with expanding foam or caulk. If the gap is too large, stuff it with fiberglass insulation, and spray foam over the top to seal the surface of the plug.
✓ Fit large openings with a rigid patch bedded in a sealant like latex caulk or foam tape, which isn’t an adhesive.
✓ Screw the patch in place, so that a plumber can remove the screws if necessary for access.
✓ Seal holes and gaps around pipes with expanding foam or caulk.
7.2.3 Stairways to Unconditioned Areas
A variety of stairways and hatchways provide access from the building to an unconditioned basement.
The following components of these stairways may need air sealing and insulation depending on whether they are at the thermal boundary.
• The risers and treads of the stairways
• The surrounding triangular walls
• Vertical or horizontal doors or hatches
• The framing and sheeting surrounding the doors or hatches
• Sloping ceilings above the stairways
Consider the following air-sealing measures.
✓ Study the geometry of the stairway and decide where to establish the air barrier and install the insulation.
✓ Weatherstrip around doors and hatches if the door or hatch is at the thermal boundary.
✓ Seal the walls, stair-stringer space, and ceiling if they are at the thermal boundary.
✓ Seal gaps around door frame or hatch frame perimeters with one-part foam, two-part foam, or caulking.
7.2.4 Incomplete Finished Basements
SWS Detail: 3.0101.1 Air Sealing Holes; 4.0402.4 Basements - Without Groundwater Leakage;4.0402.5 Basements - With Groundwater Leakage |
Discontinuous wall segments can allow heated basement air to circumvent the finished and insulated wall, carrying heat with it. Complete the finished walls or at least install air barriers between finished living area and unconditioned area between the insulated wall and the foundation wall. Here are two suggestions.
✓ Bridge the gap with wood sheeting, bedded in sealant, and caulk the crack around four sides of this long narrow patch.
✓ Stuff the gap with pieces of fiberglass batt and spray two-part foam over the gap, at least an inch thick.
See also "Basement Wall Insulation" on page 237.
Floors that hang over their lower story are called cantilevered floors. The underside of the overhanging floor can leak considerably. Many balconies and bay windows have cantilevered floors that leak air into a building’s floor cavity.
Fill Cavities with Fibrous Batts
✓ Remove a piece of soffit under the overhanging floor to determine the condition of insulation and air barrier.
✓ Stuff the overhanging floor with fiberglass or rock wool batts.
✓ Bed the sheeting underneath the overhanging floor in sealant where possible. Caulk joints and seams where the sheeting isn’t bedded in sealant.
✓ Seal any ducts you find in the cantilevered floor sections.
Dense-Pack Cavities from a Drilled Hole
✓ Drill a hole at least 1.5 inch in diameter.
✓ Dense-pack fibrous insulation into the cavity.
✓ Seal all holes and cracks with an appropriate sealant.
See also "Installing Floor Insulation" on page 228.
7.3 Preparing for Foundation or Floor Insulation
Floor and foundation insulation can increase the likelihood of moisture problems. Installers should take all necessary steps to prevent moisture problems from ground moisture before installing insulation. See also "Reducing Moisture Problems" on page 31.
7.3.1 Rim-Joist Insulation and Air-Sealing
SWS Detail: 3 Air Sealing; 4.0401.1 SPF Insulation; 4.0401.2 Batt Insulation; 4.0401.3 Rigid Insulation |
The rim-joist spaces at the perimeter of the floor are a major weak point in the air barrier and insulation. Insulating and air sealing both the rim joist and longitudinal box joist are appropriate either as individual procedures or as part of floor or foundation insulation.
Air seal stud cavities in balloon-framed homes as a part of insulating the rim joist. Air seal other penetrations through the rim before insulating. Two-part spray foam is the most versatile air sealing and insulation system for the rim joist because spray foam air seals and insulates in one step.
Polystyrene or polyurethane rigid board insulation are also good for insulating and air sealing the rim joist area. When the rim joist runs parallel to the foundation wall, the cavity may be air sealed and insulated with methods similar to those as shown here.
If you leave the spray foam exposed, it should have a flame spread of 25 or less and be no more than 3.25 inches thick according to the IRC. In habitable spaces, cover all foam with a thermal barrier such as drywall or use an insulation product that doesn’t require a thermal barrier like mineral wool boards and foil-faced PIC.
Don’t use fiberglass batts to insulate between rim joists because air can move around the fiberglass, causing condensation and encouraging mold on the cold rim joist. If you use foam to insulate between the rim joists, use liquid foam sealant to seal around the edges of the rigid foam.
7.4 Installing Floor Insulation
SWS Detail: 4.03 Floors; 4.0301 Accessible Floors; 4.0302 Exposed Floors; 3.0102.2 Sealing High-Temperature Devices |
Before installing floor insulation, make the following preparations.
✓ Seal air leaks in the floor from the living space, the crawl space, or the basement, as opportunity allows.
✓ Seal and insulate ducts remaining in the crawl space or unconditioned basement.
✓ Identify electrical junction boxes, plumbing valves, and drains before insulating, and provide access to them.
✓ Insulate water lines in cold climates if they protrude below the insulation.
✓ Treat high-temperature devices — non-IC rated recessed lights, chimneys, flues, vents — unless they are zero clearance devices as shown in “Sealing Vertical Chases and Chimneys” on page 139.
✓ Install flags that are visible below the floor joists at utility junctions for future identification and verify that utility junctions remain accessible.
✓ Post a dated receipt signed by the installer that includes: installed insulation type, coverage area, installed thickness, and installed R-value.
7.4.1 Blowing Floor Insulation
The best way to insulate a floor cavity is to completely fill each joist cavity with fiberglass insulation. Blowing fiberglass insulation is the easiest way to achieve complete coverage because the blown fiberglass is able to surround obstructions and penetrations better than fiberglass batts. Avoid blown cellulose because of its weight, moisture absorption, and tendency to settle.
✓ Cover the entire under-floor surface with a vapor permeable supporting material such as: dust-free fabric insulation restraint or equivalent vapor-permeable and drain-able material.
✓ Use wood strips to support the flexible or semi-flexible support material unless that material with its fasteners can support the floor insulation with a minimum of sagging.
✓ Install rock wool or fiberglass blowing wool through V-shaped holes in the air barrier.
✓ Use a fill tube to install the blown insulation. Insulation must travel no more than 12 inches from the end of the fill tube.
7.4.2 Installing Fiberglass Batt Floor Insulation
SWS Detail: 4.0301.1 Batt Insulation in Joisted Cavities; 4.0301.5 SPF in Open Joisted Cavities; 4.0301.7 Non-Joisted Floors Batt Insulation |
Observe these material and preparation specifications for insulating under floors.
✓ Seal all significant air leaks through the floor before insulating the floor, using strong airtight materials.
✓ Choose unfaced batts for insulating floors.
✓ Batt thickness must fill the complete depth of each cavity.
✓ Batts must be neatly installed, fitting tightly together at joints, fitting closely around obstructions, and filling all the space within the floor cavity.
✓ Insulate crawl-space access doors, adjacent to a conditioned space, to at least R-21 for horizontal openings and to at least R-15 for vertical openings.
✓ Weatherstrip crawl-space access doors, adjacent to a conditioned space.
✓ Post a dated receipt signed by the installer that includes: installed insulation type, coverage area, installed thickness, and installed R-value.
Installation Specifications for Batts in Floor Cavities
Batt insulation, installed in floors, must be supported by twine, wire, wood lath or other suitable material that keeps the insulation touching the floor. Friction-fit fiberglass batts supported by self-supporting wire insulation supports aren’t good practice because the supports often fail. Fasteners for floor insulation must resist gravity, the weight of insulation, and moisture condensation.
✓ Install batts in continuous contact with the subfloor.
✓ Cut the batts accurately and squarely. Insulation knives or electric carving knives are excellent tools for this purpose.
Use one of the following 4 restrainer materials to keep the fiberglass batts in the floor cavity.
1. Install standard wood lath (1/4 inch by 1 inch) or nominal one-inch lumber. Install the lath or lumber perpendicular to joists 12 inches apart for joists on 24-inch centers and 18 inches apart for joists on 16-inch centers.
2. Install non-stretching polypropylene or polyester strapping or twine.
3. Install copper or stainless steel wire with a minimum diameter of 0.04 inches or size 18 AWG.
4. Install a rigid vapor-permeable air barrier, such as asphalt-impregnated fiberboard.
Observe these requirements about installation and fasteners for the restrainers.
• Fasten lath or a rigid barrier with screws, nails, or power-driven staples. The fastener should penetrate the joist 3/4 inch or more.
• Install twine or wire in a zig-zag pattern.
• Install power-driven staples over the strapping, twine, or wire 12 inches apart for joists on 24-inch centers and 18 inches apart for joists on 16-inch centers. The staples must penetrate the wood joists by at least 5/8 inch. Don’t hand staple the restrainer.
7.4.3 Spray Foam & Rigid Foam Floor Insulation
SWS Detail: 4.0301.8 Non-Joisted Floors Rigid Foam; 4.0301.9 Non-Joisted Floors SPF |
Foam Material Specifications
✓ Select insulation and support materials that have a flame-spread/smoke-developed index of 75/450.
✓ Separate all foam products from living space with a thermal barrier material:1/2 gypsum wallboard or equivalent.
✓ If a crawl space is used only for servicing utilities, separate the foam from the space using an ignition barrier covering or coating, such as intumescent paint.
7.5 Foundation Wall Insulation
SWS Detail: 3.0104.1Closed Crawlspace Air Sealing; 4.0402.1 Closed Crawlspace - Non-Foam Insulation; 4.0402.2 Closed Crawlspace - Rigid Foam Insulation; 4.0402.3 Closed Crawlspace - SPF Insulation |
Crawl-space foundation insulation is only worthwhile if you can seal the existing foundation vents.
See "Ground-Moisture Barriers" on page 42.
See “Power-Ventilated Crawl Spaces” on page 450.
7.5.1 Crawl-Space Wall Insulation
Retrofit foundation insulation is usually installed on the inside of the foundation walls. Contractors undertake this retrofit for both energy savings and moisture control. See "Solutions for Moisture Problems" on page 34.
Foundation Wall Insulation Material
Observe these insulation specifications for insulating foundation walls.
• Any foam foundation-wall insulation should be labeled ASTM E84 or UL 723 with a flame spread of less than 25 and smoke developed value of less than 450.
• Protect foam insulation by intumescent paint or another ignition barrier if not labeled ASTM E84 or UL 723.
• Local building officials may approve other foam materials based on product labels such as NFPA 286, FM 4880, UL 1040, or UL 1715.
• Unfaced mineral fiber insulation, greater than 5 pounds per cubic foot in density. Although expensive, mineral wool board is probably the best choice because it is vapor permeable and non combustible.
• Metal fasteners should carry a label of ASTM B 695 Class 55.
These insulation products might meet some of the above specifications.
• Foil-faced polyisocyanurate.
• Expanded polystyrene foam board.
• Two-part high-density spray polyurethane foam with fire-retardant specifications as listed above. See "Special Safety Precautions for Spray Foam" on page 128.
• Unfaced rock wool board or fiberglass board.
.
Consider these issues with the use of fibrous insulation in crawl spaces.
• Fiberglass batts or blankets are poor choices for foundation insulation because their facing is a vapor retarder. The facing can trap moisture in the fiberglass between the foundation wall and the facing.
• Sprayed fiberglass and cellulose are easily damaged by moisture, mechanical abrasion, and adhesive failure.
Safety and Durability
Consider the following issues when insulating foundation walls.
✓ Secure outdoor access hatches to foundation walls. If the foundation walls are insulated, also insulate any crawl-space access hatch with foam to the same R-value of the foundation wall.
✓ Remove obstacles and debris from crawl space before retrofit.
✓ If an open-combustion appliance is located in a crawl space, verify that outdoor combustion air is available to the appliance.
✓ When insulating crawl-space walls, consult the local building inspector about acceptable ventilation options if in doubt. See "Crawl Space Ventilation" on page 449.
In regions affected by termites, carpenter ants, and similar insects consider these suggestions.
✓ Leave a termite-inspection zone between the foundation and the rim-joist insulation.
✓ Apply insulation with moisture control measures, pesticide, or baiting.
✓ Consult with experts to ensure that the insulation, air sealing materials, and moisture barrier don’t provide a conduit for insects to infest the wood floor.
7.5.2 Basement Wall Insulation
SWS Detail: 4.0402.4 Basements - Without Groundwater Leakage; 4.0402.5 Basements - With Groundwater Leakage; 4.0401.1 SPF Insulation |
Before installing basement wall insulation, inspect for moisture problems and take appropriate action to solve moisture problems.
✓ Check for bulk-water problems like puddling around the foundation or malfunctioning gutters and downspouts. See "Reducing Moisture Problems" on page 31.
✓ Remove obstacles and debris from the basement.
✓ Repair structural cracks in foundation walls.
✓ Install a drainage system with a sump and outdoor drainage as appropriate to solve major moisture problems.
Basement wall insulation is often installed ineffectively because of the installers’ incomplete understanding about moisture problems.
The most common (although not the best) way to insulate basement walls, or any masonry wall, is to build a framed wall against the masonry wall and fill the wall with fiberglass batts. The frame wall is then covered with drywall.
Unfaced batts are the best choice of fiberglass insulation since they contain no vapor barrier to trap moisture. Moisture may escape from the wall in either direction: from outdoors in or indoors out.
With a framed wall, the installer often neglects to seal in areas where the wall is discontinuous, such as a mechanical room. Any area, such as an unfinished wall, open rim-joist area, or un-sheeted ceiling, constitutes a very large air leak around the insulated wall. Avoid this problem by doing these procedures.
✓ Insulate the rim joist and air seal it.
✓ Build the frame walls.
✓ Wall off the entire basement. If a mechanical room or other area won’t be insulated, install an airtight block at the wall’s edge to prevent basement air from circulating behind the insulated wall.
✓ Don’t install a vapor barrier on the interior face of the new basement wall unless you use rigid foam. The new wall assembly must be able to dry toward the indoors or to the outdoors.
✓ Install drywall in an airtight manner on the walls and ceiling by applying sealant to the framing lumber around the sheet’s perimeter.
Stripped Foam Basement Insulation
Polystyrene foam is an excellent choice for insulating smooth basement walls.
You can order either expanded polystyrene or extruded polystyrene equipped with grooves for fastening strips, spaced apart on 16-inch or 24-inch centers. Stripped foam sheets may be the easiest and most satisfactory way to insulate below-grade basement walls. Do these procedures to install 2-inch stripped foam on a foundation wall.
✓ Apply walnut-sized globs of adhesive to the back of the sheet on one-foot centers. Use a foam-compatible adhesive and follow the instructions on the container.
✓ Install at least two concrete screws or two powder-driven nails in each strip, 24 inches from the bottom and top.
✓ Wherever an electrical box is needed, install it between two sheets if possible because it’s easier to run the wire between sheets than toward the center of a sheet. Install an electrical box backed by a piece of treated wood that sets the box out from the foam a half inch to accommodate the thickness of the wallboard that will be installed over the foamboard. Use construction adhesive and a concrete screw to fasten the box in place.
✓ Leave a half-inch gap at the bottom of the polystyrene sheets to run wire. Run the wire along the floor and up into the boxes. If flooding is a possibility, run the wire at the ceiling and down into boxes on the wall.
✓ Seal the bottom gap and other gaps in the foam sheeting with one-part foam.
✓ Glue the drywall using the same adhesive and pattern. Screw the drywall to each wooden strip with one-inch drywall screws.
Exterior Foam Foundation Insulation
If installed at the exterior, as during new construction, use durable water-resistant insulation such as blue or pink extruded polystyrene or high-density (2 pcf) expanded polystyrene. For portions that are exposed above ground level and six inches below ground, you’ll need to provide mechanical and moisture protection such as sheet metal or fiberglass panels. For areas more than 6 inches below grade, there are asphalt-based sealants for the foam that you apply with a paint roller.
See also "Insulated Wall Sheathing" on page 211.