Chapter 5:                      Walls

This chapter discusses air sealing and insulation for walls in existing buildings. Air sealing begins by inspecting the disconti­nuities in walls, such as the following.

       Inside and outside corners of walls.

       Openings for windows and doors.

       Protrusions and indentations in walls.

Insulation begins by evaluating the existing wall insulation and deciding on the feasibility and cost-effectiveness of installing additional wall insulation. Other wall-insulation issues may include the following.

       Whether you can install wall insulation at all, such as in walls already partially insulated.

       Whether to insulate from interior or exterior of the home.

       How to open a wall cavity and restore it after insulating the wall cavity.

       How to install insulation to the wall’s surface.

5.1   Air Sealing Walls

SWS Detail: 3.1001.3 Walls Open to Attic—Balloon Framing and Double Walls, 3.1102.1 Wall Penetration Sealing, 3.1001.6 Fire­wall in Unconditioned Attic, 3.1001.7 Firewall in Conditioned Attic, 3.1802.1 Roof/Exterior Wall Connection, Including Joints at Roof/Parapet/Wall Connections

Most wall air leakage involves the wall’s discontinuities, joints, and irregularities.

5.1.1   Multifamily Firewalls

Firewalls are structural walls between buildings or dwelling units that prevent the spread of fire from one unit to another. Air-sealing between building materials on the two sides of the fire wall and the fire wall itself is an important safety and energy-conservation task.

     When air-sealing, preserve existing fire ratings of materi­als and assemblies along with existing-material compati­bility and comparable durability.

     Verify that non-monolithic fire walls, such as balloon-framed walls, are airtight assemblies both to air flowing horizontally and vertically. Improve airtightness as neces­sary through air sealing and dense-packing with fibrous insulation.

     Seal air channels, created by furring strips or wall framing, against a monolithic firewall. At a minimum seal the top and bottom of each channel, and/or densepack the chan­nels with fibrous insulation.

     Seal gaps and cracks with air-sealing materials and back­ing materials that are compatible with and similar to exist­ing materials with fire-containment functionality.

See Air Sealing and Fire Containment See Balloon Framed Walls See Fire Testing and Rating See Fire Safety

5.1.2   Built-In Cabinets/Shelves

Built-in cabinets and shelves are a feature of older homes and present challenges for air sealing. Sealing these areas from inside the cabinet requires care and attention to appearances.

     If possible, establish both an air barrier and insulation behind the cabinet, out of sight of the occupants.

     Install drywall or wood wherever the cabinet is open to a wall cavity after insulating the cavity.

     Use caulking that is compatible with the colors of the sur­rounding wood if you seal its interior-facing side.

Built-inCab.jpg

 

5.1.3   Wall Framing Around Fireplaces and Chimneys

1.SWS Detail: P3.1001.1 Penetrations and Chases, 3.1001.3 Walls Open to Attic—Balloon Framing and Double Walls

Leaks around fireplace chimneys are often severe air leaks. Use this procedure to seal air leaks through the chimney chase.

     Cut 26 gauge galvanized sheet metal to fit the gap that bor­ders the chimney with overlaps connecting to nearby framing lumber.

     Bed the sheet metal air seal in sealant (ASTM E136), and then fasten the sheet metal to the framing with staples, nails, or screws.

     Seal the metal patch to chimney or flue with a non-com­bustible sealant.

     For large chimney chases, cover the chase opening with structural material such as plywood. Maintain clearances between the structural seal and the metal or masonry chimney as listed in Clearances to Combustibles for Common Chimneys.

FirePlceFrming.jpg

 

5.1.4   Pocket Door Cavities

SWS Detail: 3.1201.4 Pocket Door

Create a fireblocking air seal at the top of the door using materi­als that won’t sag. When located on the second floor, cap the top of the entire wall cavity in the attic with rigid board, caulked and mechanically fastened.

5.1.5   Cooling Appliances Installed through Walls or Windows

Room air conditioners, room heat pumps, and evaporative cool­ers are sometimes installed through walls or in windows. The units installed in windows are often very leaky because of the temporary nature of the air seals.

room_ac_cover.jpg

 

       Remove window units in the fall and re-install in the spring.

       If the client doesn’t want to remove the unit seasonally, cover the unit with a room-air-conditioner cover as shown here.

       Units installed through walls should have a sheet-metal sleeve that seals well to the surrounding framing and finish. This metal sleeve provides a smooth surface to seal to the room air conditioner or heat pump.

       Seal the unit’s perimeter with one-part foam or caulking, depending on the width of the joint.

5.1.6   Balloon Framed Walls

SWS Detail: 3.1001.3 Walls Open to Attic—Balloon Framing and Double Walls, 4.1103.4 Dense Packing Blown Insulation

Balloon framed two-story walls are common in older homes. Some modern homes have balloon framed gable walls, where the studs rise above the level of the ceiling joists and are cut at an angle to frame the gable. Even when these balloon framed gable walls are full of insulation, air can convect through the insula­tion. On occasion, windstorms have blown the insulation out of the wall cavity into the attic.

Walls00007.jpg

 

     Dense-pack insulation into the wall cavities to reduce air leakage and convection.

     Dense-pack insulation into an air-permeable bag inserted with the fill tube into the balloon-wall floor cavity.

     Seal stud cavities from the attic, basement, or crawl space with a insulation plug, covered with a 2-part-foam air seal.

     Or seal the tops and bottoms of cavities with a rigid bar­rier, such as drywall or plywood, sealed and bonded to surrounding materials with 2-part foam.

See also Wall Insulation

Walls00010.jpg

 

5.2   Minor Air Sealing

Minor air sealing includes sealing small openings with such materials as caulk or weather stripping.

5.2.1   Window and Door Frames

Sealing from the exterior serves to keep bulk water out and pro­tect the building. If the crack is deeper than 5/16-inch, it should be backed with a material such as backer rod and then sealed with caulk. Any existing loose or brittle material should be removed before the crack is re-caulked. See also Windows and Doors

SlicneBulbs.jpg

 

5.2.2   Rim Joist Area

The rim joist area is composed of several joints. They can be sealed from the basement or crawl space with caulk or foam. Remove dust before applying sealant. See also Rim-Joist Insulation and Air-Sealing

5.2.3   Masonry Surfaces

Masonry surfaces are best sealed with a cement-patching com­pound, mortar mix, or high quality caulking, such as polyure­thane. For cement-based patches, buy a mix designed for patching and prime the damaged areas with a concrete adhesive.

5.2.4   Interior Wall Top Plates

Drywall is installed after interior walls are constructed. The top plates of interior walls are open to the attic. Top plate shrinkage opens up cracks that run the entire length of the interior wall. Move insulation and seal the cracks with caulking or two-part foam.

Walls00015.jpg

 

5.3   Wall Insulation

Install wall-cavity insulation with a uniform coverage and den­sity. Wall cavities encourage airflow like chimneys. Convection currents or air leakage can significantly reduce wall insulation’s thermal performance if channels remain for air to migrate or convect.

Important: Provide the client with an insulation receipt or cer­tificate, with insulation type and number of bags installed, installed thickness, coverage area, and insulation R-value. See Insulation Receipt or Certificate

Blown Wall-Insulation Types

Cellulose, fiberglass, and open-cell polyurethane foam are the leading insulation products for retrofit-installation into walls.

Table 5-1:         Wall Insulation Density and R-Value per Inch

Insulation Material

Density

R-Value/in.

Fiberglass (virgin fiber)

2.2 pcf

4.1

Cellulose

3.5 pcf

3.4

Open-cell urethane foam

0.5 pcf

3.8

pcf = pounds per cubic foot

5.3.1   Wall Insulation: Preparation and Follow-up

SWS Detail: 4.1101.1 Exterior Wall Dense Packing, 4.1101.2 Exterior Wall Insulating Sheathing, 4.1101.3 Exterior Wall Spray Polyurethane Foam (SPF)—Masking and Surface Preparation, 4.1101.4 Exterior Wall Spray Polyurethane Foam (SPF)—Electrical System Considerations, 4.1103.2 Additional Exterior Wall Cavities

Inspect and repair walls thoroughly to avoid damaging the walls, blowing insulation into unwanted areas, or causing a dust hazard.

Preparing for Wall Insulation

Before starting to blow insulation into walls, take the following preparatory steps.

     Calculate how many bags of insulation are needed to achieve the R-value specified on the bag’s label.

     Inspect walls for evidence of moisture damage. If an inspection of the siding, sheathing, or interior wall finish shows a moisture problem, don’t install sidewall insulation until the moisture problem is identified and solved.

     Inspect indoor surfaces of exterior walls to assure that they are strong enough to withstand the force of insulation blowing. Reinforce interior sheeting as necessary.

     Inspect for interior openings or cavities through which insulation may escape. Examples include balloon-framing openings in the attic or crawl space, pocket doors, un-backed cabinets, interior soffits, and openings around pipes under sinks, and closets. Seal these openings to pre­vent insulation from escaping the wall cavity.

     Verify that exterior wall cavities aren’t used as return or supply ducts. Either avoid insulating these cavities, or re-move the ducts and reinstall them somewhere else.

     Verify that electrical circuits inside the walls aren’t over­loaded. Maximum ampacity for 14-gauge copper wire is 15 amps and for 12-gauge copper wire is 20 amps. Install S-type fuses to prevent circuit overloading if necessary. Don’t insulate cavities containing knob-and-tube wiring. See Electrical Safety

ballon_framing_pflow.jpg

 

Patching and Finish after Insulating

The insulators, the home owner, and others should agree about the patching method and the final appearance of the wall finish. The insulators are usually responsible for patching holes and returning the interior or exterior finish to its previous condition or some pre-agreed level of finish.

     Patch the exterior wall sheathing with wood plugs, plastic plugs, or spray foam insulation.

     Use caulk or putty and primer to dress exposed exterior plugs.

     Seal gaps in external window trim and other areas that may admit rain water into the wall.

     Patch interior finish with standard plastering methods or a chair rail trim board.

     Install drywall with joint compound to open cavities to comply with IRC fire codes.

Wall Insulation Quality Control

Retrofit wall insulation has more risk of incomplete application than insulation that you can visually inspect. Consider these quality control options to verify the proper coverage and density of retrofit wall insulation.

       Viewing the wall through an infrared camera.

       Looking through an electrical outlet or other access hole for insulation.

       Calculation of installed weight of installed insulation com­pared to wall-cavity volume and required density.

Walls00020.jpg

 

Drilling Exterior Sheathing: Insulation Retrofit

Avoid drilling through siding. Where possible, carefully remove siding and drill through sheathing. This procedure avoids the potential lead-paint hazard of drilling the siding. Drilling through only the sheathing also makes it easier to insert flexible fill tubes since the holes pass through only one layer of material.

If you can’t remove the siding, consider drilling the walls from inside the home. Obtain the owner’s permission before drilling indoors, and practice lead-safe weatherization procedures. See this locaiton.

Consider these possible methods of removing siding.

       Cut completely through the paint on wood-siding joints with a sharp utility knife before carefully prying the siding off.

       Remove asbestos shingles by pulling the nails holding the shingles to the sheathing, or else cut off the nail heads. Dampen the asbestos tiles to reduce dust. Wear a respirator and coveralls when working with asbestos siding.

       Use a zip tool to remove metal or vinyl siding.

       Insulate homes with brick veneer or blind-nailed asbestos siding from the indoors.

       Use a decorative chair rail to cover holes drilled indoors.

Restore holes drilled for insulation to an appearance as close to original as possible, or in a manner that is satisfactory to the cli­ent.

AsbSidingRemov.jpg

 

5.3.2   Retrofit Closed-Cavity Wall Insulation

SWS Detail: 4.1103.1 Dense Pack Exterior Walls, 4.1103.2 Additional Exterior Wall Cavities, 4.1103.4 Dense Packing Blown Insulation

This section describes six ways of installing wall insulation.

1.      Blowing walls with fibrous insulation using a fill tube from indoors or outdoors.

2.      Installing batts in an open wall cavity.

3.      Injecting liquid foam into a closed wall cavity.

4.      Spraying wet-spray fiberglass or cellulose into an open wall cavity.

5.      Spray open-cell or closed-cell foam into an open wall cavity.

6.      Blowing fibrous insulation behind netting.

Blowing Walls with a Fill-Tube

Install dense-pack wall insulation using a blower equipped with separate controls for air and material feed. Mark the fill tube in one-foot intervals to help you verify when the tube reaches the top of the wall cavity.

Walls00025.jpg

 

To prevent settling, cellulose insulation must be blown to at least 3.5 pounds per cubic foot (pcf) density. Fiberglass dense-pack must be 2.2 pcf and the fiberglass material must be designed for dense-pack installation.

Insulate walls using this procedure.

1.      Drill 2-to-3-inch diameter holes to access the stud cav­ity.

2.      Probe all wall cavities through holes, before you fill them with the fill tube, to identify fire blocking, diago­nal bracing, and other obstacles.

3.      Start with several full-height, unobstructed wall cavities so you can measure the insulation density and calibrate the blower. An 8-foot cavity (2-by-4 on 16-inch centers) should consume a minimum of 10 pounds of cellulose or 6 pounds of fiberglass.

4.      Insert the hose all the way to the top of the cavity. Start the machine, and back the hose out slowly as the cavity fills.

5.      Then fill the bottom of the cavity in the same way.

6.      After probing and filling, drill whatever additional holes are necessary for complete coverage. For example: above windows, missed areas with fire blocking.

7.      Use the blower’s remote control to achieve a dense pack near the hole while limiting spillage.

8.      Seal and plug the holes, repair the weather barrier, and replace the siding.

Insulating the Wall-Floor Junction of Two-Story Walls

When insulating the perimeter of walls between the first and second floors, blow an insulation plug into the perimeter floor cavities for both thermal resistance and airflow resistance. This method is particularly effective for platform-framed walls because the wall insulation is discontinuous at the floor cavity unless you drill and blow through the rim joist there.

This insulation plug prevents the floor cavity from being a ther­mal bridge and an air-leakage conduit. Using a fill tube, blow the insulation into a air-permeable bag that expands inside the cav­ity. This is often referred to as a “bag-and-blow”. The bag limits the amount of insulation necessary to insulate the floor perime­ter.

B-WJunctionF-Wbag.jpg

 

Injecting Liquid Foam

Injecting liquid foam is more expensive than blowing fibrous insulation but offers better performance when existing walls are partially filled by batts. The batts are often 1-to-2 inches thick and are usually flush with the interior or exterior wall surface. Try injecting the foam from outdoors to fill the cavity and com­press the batt slightly. From indoors, the foam may just stretch the batt facing and fail to create a fully insulated wall cavity.

Open-cell polyurethane foam, formulated to expand less than the sprayed variety, is the leading wall-retrofit foam. Techni­cians install the foam through holes (<1 inch) spaced about two feet apart using a simple nozzle that barely enters the cavity. Technicians use drinking straws or other indicators to judge the level that the foam has filled during installation. Technicians don’t normally use fill tubes to inject open-cell foam because the tube would be too difficult to clean.

See Fire Protection for Foam Insulation

video_play_button.png

 

5.3.3   Open-Cavity Wall Insulation

SWS Details: 4.1102.1 Open Wall Insulation—General, 4.1102.2 Open-Cavity Wall—Spray Polyurethane Foam (SPF) Installation

Fiberglass batts are the most common open-cavity wall insula­tion. Batts achieve their rated R-value only when installed care­fully. If there are gaps between the cavity and batt at the top and bottom, the R-value can be reduced significantly. The batt should fill the entire cavity without spaces in corners or edges.

Walls00032.jpg

 

     Use unfaced friction-fit batt insulation where possible. Fluff the batts during installation to fill the depth of the wall cavity.

     Choose medium- or high-density batts: R-13 or R-15 rather than R-11, and R-21 rather than R-19.

     Seal all significant cracks and gaps in the wall structure before or after you install the insulation.

     Insulate behind and around obstacles with scrap pieces of batt before installing batts.

     Staple faced insulation to outside face of studs on the warm side of the cavity. Don’t staple the facing to the side of the studs, even though drywallers may prefer that method, because this method leaves an air space that encourages convection currents.

     Cut batt insulation to the exact length of the cavity. A too-short batt creates air spaces above and beneath the batt, allowing convection. A too-long batt bunches and folds, creating air pockets.

     Split batt around wiring, rather than letting the wiring compress the batt to one side of the cavity.

     Fiberglass insulation, exposed to the interior living space, must be covered with minimum half-inch drywall or other material that has an ASTM flame spread rating of 25 or less.

     Fiberglass batts exposed to unoccupied spaces like attics must be covered with an air barrier such as house wrap or foam sheeting to prevent R-value degradation by convec­tion and human exposure to fibers.

See Fiberglass Batts and Blankets

Walls00035.jpg

 

Blowing Open Wall Cavities behind Netting or Fabric

Blowing dry fibrous insulation behind netting or fabric is a common way of insulating open walls before drywall applica­tion, especially with cellulose. However, you must install the insulation to a sufficient density to resist settling.

     Verify density of at least 3.5 pcf for cellulose or 2.2 pcf for fiberglass.

     Select a restrainer netting or fabric that will allow the above densities without bulging excessively.

     Fasten the netting or fabric with power-driven staples, 1.5 inches apart.

     Roll bulging insulation with a roller to facilitate drywall installation.

Walls00038.jpg

 

5.3.4   Insulating Unreinforced Brick Walls

SWS Detail: 4.1103.3 Insulated Sheathing and Insulated Siding Installation

Unreinforced means that the builders used no steel or other metal reinforcement. There are three types of unreinforced brick walls.

1.      Traditional brick walls with header bricks that hold two layers of stretcher bricks together. Larger buildings may have three or more brick layers instead of two.

2.      Various types of hollow brick walls with usually one layer of brick on either side of an air space.

3.      Wood-frame brick veneer walls with a single layer of brick veneer that is attached to a typical wood frame wall.

All three of these brick assemblies may have structural problems depending on the condition of the bricks and mortar joints. Mortar can turn to dust over the decades; hollow brick walls can be frighteningly fragile; and small movements can topple 100-year-old brick veneer. Consult a structural engineer before making any modification to an unreinforced brick building.

DblBrkWall.jpg

 

Insulation Receipt or Certificate

Provide the client with an insulation receipt or certificate, with insulation type and number of bags installed, installed thick­ness, coverage area, and insulation R-value. See Insulation Receipt or Certificate

5.4   SWS Alignment

Field Guide Topic

SWS Detail

5.1: Air Sealing Walls - Pg. 165

 3.1001.3 Walls Open to Attic—Balloon Framing and Double Walls,
3.1102.1 Wall Penetration Seal­ing,
3.1001.6 Firewall in Uncondi­tioned Attic,
3.1001.7 Firewall in Conditioned Attic,
3.1802.1 Roof/Exterior Wall Con­nection, Including Joints at Roof/Parapet/Wall Connections

5.1.1: Multifamily Firewalls - Pg. 166

N/A

5.1.2: Built-In Cabinets/Shelves - Pg. 166

N/A

5.1.3: Wall Framing Around Fire­places and Chimneys - Pg. 167

3.1001.1 Penetrations and Chases,
3.1001.3 Walls Open to Attic—Balloon Framing and Double Walls

5.1.4: Pocket Door Cavities - Pg. 168

3.1201.4 Pocket Door

5.1.5: Cooling Appliances Installed through Walls or Windows - Pg. 168

N/A

5.1.6: Balloon Framed Walls - Pg. 169

3.1001.3 Walls Open to Attic—Balloon Framing and Double Walls,
4.1103.4 Dense Packing Blown Insulation

5.2: Minor Air Sealing - Pg. 171

N/A

5.2.1: Window and Door Frames - Pg. 171

N/A

5.2.2: Rim Joist Area - Pg. 172

N/A

5.2.3: Masonry Surfaces - Pg. 172

N/A

5.2.4: Interior Wall Top Plates - Pg. 172

N/A

5.3: Wall Insulation - Pg. 173

N/A

5.3.1: Wall Insulation: Prepara­tion and Follow-up - Pg. 174

4.1101.1 Exterior Wall Dense Packing,
4.1101.2 Exterior Wall Insulating Sheathing,
4.1101.3 Exterior Wall Spray Polyurethane Foam (SPF)—Masking and Surface Preparation,
4.1101.4 Exterior Wall Spray Polyurethane Foam (SPF)—Electrical System Considerations

5.3.2: Retrofit Closed-Cavity Wall Insulation - Pg. 178

4.1103.1 Dense Pack Exterior Walls,
4.1103.2 Additional Exterior Wall Cavities,
4.1103.4 Dense Packing Blown Insulation

5.3.3: Open-Cavity Wall Insulation - Pg. 182

4.1102.1 Open Wall Insulation—General,
4.1102.2 Open-Cavity Wall—Spray Polyurethane Foam (SPF) Installation

5.3.4: Insulating Unreinforced Brick Walls - Pg. 185

4.1103.3 Insulated Sheathing and Insulated Siding Installation